<< back |
|
klick here for dimensions |
| |
|
|
|
| |
H05V-K |
|
PVC insulated wiring |
| |
H05V-K |
|
PVC insulated single conductor |
 |
| |
Construction |
|
|
| |
Conductor |
|
tinnde copper strands acc.to DIN VDE 0295 class5 IEC 60228 class5 - HD 383 class5 |
| |
Insulation |
|
PVC acc.to DIN VDE 0281 part1 |
| |
Sheath colour |
|
black |
| |
|
|
|
| |
Technical data |
|
|
| |
Nominal voltage |
H05V2-K |
|
DIN VDE |
UL/CSA |
| |
|
H05V-K |
|
Uo/U 300/500V |
600V |
| |
Nominal voltage |
H07V2-K |
|
DIN VDE |
UL/CSA |
| |
|
H07V-K |
|
Uo/U 450/750V |
600V |
| |
Testing voltage |
H05V2-K |
|
2000V acc. to DIN VDE 0281 part2 + |
| |
|
H05V-K |
|
HD21.1 |
| |
Testing voltage |
H07V2-K |
|
2500V acc. to DIN VDE 0281 part2 + |
| |
|
H07V-K |
|
HD21.2 |
| |
Min. bending radius |
|
|
| |
fixed laying |
|
4 x d |
| |
flexible application |
|
6 x d |
| |
Temperature range |
|
DIN VDE |
UL/CSA |
| |
fixed laying |
|
-40°C / +90°C |
up to -105°C |
| |
flexible application |
|
+5°C / +90°C |
up to -105°C |
| |
Fire performance |
|
flame retardant and self-extinguishing |
| |
|
|
acc. to IEC 60332-1 UL VW-1 and CSA FT1 |
| |
|
|
|
| |
Outstanding features |
|
|
| |
LiY : 250V |
|
|
| |
H05V-K : 300/500V |
|
|
| |
H07V-K : 450/750V |
|
|
| |
flexible single wire |
|
|
| |
harmonised acc.to European standards |
| |
|
| |